Horizontal Mounting Derating Rules for DIN Rail Power Supplies

Horizontal mounting is a real 24 V DC power question, not a minor bracket choice. The practical decision is whether the orientation is allowed, how much output remains after derating, and whether that output still covers the cabinet load at the local enclosure temperature.
Horizontal mounting
Derating curve
24 V DC load
Cabinet ambient
Power margin
First decision
Is the orientation allowed?
Final decision
Derated output versus load
Direct answerIf the datasheet allows horizontal or sideways mounting, read the specific derating curve and recalculate the usable output. If the manual allows only vertical mounting, do not use a percentage rule to justify a horizontal installation.
Horizontal mounting derating curve for a DIN rail power supply

The Page Answer in One Minute

A DIN rail power supply is normally cooled by natural convection. Its housing, vents and internal heat path are usually designed around a stated mounting position. When the unit is turned sideways or mounted horizontally, warm air may no longer leave the supply in the same way.

The correct engineering sequence is simple: confirm the allowed orientation, check the clearances, read the orientation derating curve, calculate the remaining watts or amps, then compare that value with the real 24 V DC load in the cabinet.

Rules of thumb are useful only as a warning. They are not a replacement for the installation manual, because one manufacturer may provide a horizontal curve, another may give a fixed reduction, and another may state vertical mounting only.

Decision table

What the documentation says

FindingAction
Horizontal mounting allowed with a curveUse the curve at the cabinet ambient near the supply.
Other orientations allowed with a fixed reductionApply the reduction and document the remaining output.
Only vertical mounting shownTreat horizontal mounting as unsupported until proven otherwise.
Horizontal mounting prohibitedChange the layout or select a different approved supply.
Cabinet ambient temperature and clearance around a horizontally mounted 24 V power supply
Local temperature
Use the surrounding air temperature beside the power supply, not the room temperature outside the enclosure. Nearby drives, transformers, contactors and cable ducts can make the supply location much warmer than the cabinet door area.

Why Horizontal Mounting Changes the Rating

The output label on a DIN rail supply is tied to stated operating conditions. Orientation is one of those conditions when the manufacturer defines a normal mounting position or gives separate derating data for other positions.

In a vertical installation, warm air can rise through and around the housing in the direction expected by the design. A horizontal position can interrupt that path, trap heat beside internal components or push warm air toward terminals and cable ducts.

The result is not always immediate failure. More often it is reduced continuous output margin, earlier thermal protection, shorter component life, DC OK alarms under load or faults that appear only after the cabinet has warmed up.

Manufacturer Data: What Usually Exists

Manufacturer documents present this information in different ways: a curve, a fixed reduction, a clearance note or a strict orientation limit. Treat the table as an evidence checklist, not as a substitute for the exact datasheet.
Source patternUseful dataHow to apply it
PULS selection guidanceHorizontal installation can impair airflow and may require derating.Use the exact product datasheet and any approved mounting accessory before changing orientation.
PULS orientation curvesSome product data gives output-current curves for alternative orientations.Read the curve for the installed position, not only the nameplate current.
Delta horizontal derating exampleA 240 W CliQ II example gives horizontal derating above 40 °C at 2.5% per °C.Use the stated start temperature and slope only for the model family that publishes it.
Phoenix Contact product dataProduct data can specify mounting position, spacing and clearance requirements.Do not calculate output margin until the real cabinet clearance is known.
Vertical-only manual exampleSome manuals state that horizontal or upside-down mounting is not allowed.Do not invent a derating factor. Reposition the supply or select a model approved for the layout.

Series Examples: How Horizontal Mounting Rules Differ

There is no universal percentage for horizontal DIN rail power supply derating. The usable output depends on the exact series, mounting orientation, cabinet temperature and the manufacturer’s own installation data.
Series or example What the data says How to read it in a cabinet
Delta CliQ III 24 V / 240 W class Horizontal mounting derating starts above 40 °C, with power reduced by 2.5% per °C in the example datasheet. A 240 W supply is not automatically a 240 W supply when mounted horizontally in a warm enclosure. At 55 °C, the usable output can be much lower than the nameplate rating.
Delta CliQ II 240 W class The datasheet separates vertical and horizontal mounting curves, with horizontal operation derating earlier than normal vertical mounting. The mounting position changes the thermal limit. Use the horizontal curve, not the vertical curve, when the unit is rotated.
PULS compact DIN rail supplies Horizontal installation can impair airflow, and derating may be necessary when the supply cannot be installed in its standard vertical orientation. Treat horizontal mounting as a thermal design condition. Check whether the selected model gives an orientation curve, a reduced current limit or a lower maximum ambient temperature.
Moxa HDR-60-24 type installation The installation guide allows vertical mounting only and states that horizontal, upside-down or table-top mounting is not allowed. No derating calculation solves a forbidden orientation. The cabinet layout or supply selection must change.
Small enclosed 24 V DIN rail supplies Some series specify larger clearances for horizontal mounting or warn that the enclosure can become hot under load. Clearance is part of the rating. A supply squeezed against wiring duct, relays or another heat source may fail the installation condition even if the load current seems acceptable.
Important reading rule
Do not copy a derating percentage from one brand to another. One manufacturer may give a horizontal derating curve, another may require reduced output current, and another may forbid the orientation completely. The correct answer starts with the exact model datasheet.

Horizontal Mounting Derating Calculator

Use this calculator to read a datasheet derating curve. Enter the rated output, the cabinet ambient temperature at the power supply, the temperature where the horizontal curve starts to derate, and the reduction rate from the manufacturer data.

The default example uses a 240 W, 24 V supply with horizontal derating above 40 °C at 2.5% per °C. At 55 °C, the remaining output is about 150 W, or about 6.25 A at 24 V DC.

Formula: usable output = rated output × [1 − ((ambient − derating start) × reduction rate ÷ 100)]. If ambient is below the start temperature, no temperature reduction is applied by this formula.
Reduction37.5%
Usable output150 W
Usable current6.25 A
Use 100% in the last field when the datasheet already gives a temperature curve. Use a lower value only when the manufacturer gives a fixed orientation allowance in addition to the temperature rule.

Worked Example: 240 W Supply at 55 °C

StepValueResult
Rated output240 W at 24 V DCNameplate current is 10 A before derating.
Horizontal curve starts40 °CNo reduction below this point in the example curve.
Cabinet ambient at supply55 °C15 °C above the horizontal derating start.
Reduction rate2.5% per °C15 × 2.5% = 37.5% reduction.
Remaining output62.5% of 240 W150 W available for continuous load.
Remaining current150 W ÷ 24 VAbout 6.25 A before any additional design margin.
What the number means
A 10 A supply in this example behaves like a 6.25 A continuous supply at the stated temperature and orientation. The cabinet is acceptable only if the real continuous load, known peaks and reserve margin fit inside that reduced value.

Load Budget After Derating

The reduced wattage has to be checked against the actual cabinet load. The thermal calculation alone does not prove that the 24 V rail still has enough operating margin.
Load groupWhat to countWhy it changes the decision
PLC and I/OCPU, digital modules, analogue modules and any module-fed field devices.The permanent control load may be larger than the CPU label suggests.
HMI and network devicesHMI, switch, gateway, router, remote I/O adapter.These loads often reset first when the rail dips.
Sensors and field devicesContinuous sensor current plus simultaneously active devices.Many small field loads can consume the derated margin quietly.
Relay and contactor coilsHolding current and pull-in demand during the operating sequence.Short peaks can trip or sag a thermally marginal supply.
Spare capacityDocumented reserve, not an unlimited spare allowance.After horizontal derating, spare capacity can disappear completely.

Inspection Sequence for a Horizontal Installation

StepEvidence to collectDecision
1. Identify the exact supplyManufacturer, part number, output rating and document revision.Use data for the installed model, not a similar-looking unit.
2. Confirm orientation permissionInstallation manual, datasheet, accessory notes or manufacturer statement.If the position is not permitted, change the layout or the supply.
3. Check clearancesTop, bottom, side clearance, cable duct distance and nearby heat sources.Blocked airflow can make a permitted position unsuitable.
4. Measure local ambientTemperature beside the supply after the cabinet has warmed up.Use this value for the curve, not room temperature.
5. Calculate derated outputRemaining watts or amps from the manufacturer rule.This is the usable continuous supply capacity.
6. Compare the loadMeasured continuous current, known peaks and backed-up loads.The cabinet needs margin after derating, not only a pass at idle.

Design Options When the Number Is Too Low

OptionWhen it helpsWhat still needs checking
Move the supply to a vertical positionThe cabinet has another rail position with better natural airflow.Input routing, output routing, service access and separation from heat sources.
Use a supply approved for side mountingThe enclosure is shallow or the DIN rail layout cannot be changed easily.The exact accessory, curve, clearance and model-specific rating.
Select a larger or higher-temperature supplyThe derated output is close to the real load.Branch protection, conductor sizing, fault-current capability and heat produced by the larger unit.
Split the 24 V loadOne supply is thermally marginal or noisy loads disturb sensitive devices.Common reference, protection selectivity, diagnostics and shutdown behaviour.
Improve enclosure ventilationThe orientation is permitted and local ambient temperature is the limiting factor.Filter condition, airflow path, fan failure behaviour and actual temperature at the supply.

Faults That Point Back to Orientation and Heat

Warm resetPLC, HMI or network devices reset only after the enclosure has been operating for a while.
DC OK flickerThe DC OK signal drops during high load or high ambient periods and recovers after the load falls.
Nuisance overloadThe supply enters protection although the nameplate rating appears higher than the connected load.
Short service lifeThe cabinet works at commissioning but the supply fails early because internal temperature stays high.
False replacementThe same supply is replaced in the same orientation, so the cabinet repeats the same thermal fault.
Load-end voltage dipThe supply output looks acceptable, but the farthest device sees a dip during warm operation or switching.

Common Mistakes

MistakeWhy it failsBetter check
Using only the nameplate currentThe label does not cover every orientation and enclosure temperature.Use the derated output for the actual mounting position.
Copying a forum percentageThe correct curve depends on housing design, product family and cooling path.Use the model-specific datasheet or installation manual.
Ignoring cable ductsDuct walls can block the airflow that the curve assumes.Check clearance after the cabinet is fully wired.
Using room temperatureThe air at the supply may be much warmer than the room.Measure near the supply after warm-up.
Oversizing without protection reviewA larger supply can change available fault current and branch-protection needs.Review conductor size, fusing, electronic protection and load grouping.

Related Reading

Horizontal derating belongs inside the wider cabinet power path: supply sizing, 24 V distribution, cabinet temperature and measured load voltage.

Common Questions

Can a DIN rail power supply be mounted horizontally?

Only when the manufacturer documentation allows that orientation. If the manual allows only vertical mounting, a derating calculation is not a substitute for an approved installation position.

Why does horizontal mounting require derating?

Horizontal mounting can disturb the intended convection path through the housing. Less effective cooling raises internal component temperature, so the continuous output power or allowed ambient temperature may need to be reduced.

Is there one derating percentage for all DIN rail power supplies?

No. Some datasheets give an orientation-specific curve, some give a fixed reduction, and some prohibit horizontal mounting. The product datasheet or installation manual controls the decision.

How do I calculate horizontal mounting derating?

Use the rated output, the cabinet ambient temperature at the supply, the derating start temperature and the reduction rate from the manufacturer curve. The remaining output is then compared with the real continuous 24 V load.

Does a 240 W supply still deliver 240 W when mounted sideways?

Not automatically. A 240 W label is valid under the stated mounting and temperature conditions. In another orientation or a hot cabinet, the usable continuous output may be lower.

What if the datasheet has no horizontal mounting curve?

Treat the orientation as unproven. Check the installation manual, product accessories and manufacturer guidance before using the device horizontally in a cabinet.

Can extra ventilation remove the need for derating?

Better ventilation can lower the surrounding air temperature at the supply, but it does not override a manufacturer orientation limit. The installation still has to match the allowed mounting position and clearances.

When is a larger power supply the wrong fix?

A larger supply is the wrong fix if the selected model is still not approved for the installed orientation, if branch protection becomes unsuitable, or if the cabinet still traps heat around the supply.